Categories | Portable Cable Fault Location System |
---|---|
Brand Name: | XZH TEST |
Model Number: | XHGG502A2+XHDD503C+XHHV535-2L |
Certification: | CE ISO |
Place of Origin: | China |
MOQ: | 1 Set |
Payment Terms: | T/T |
Delivery Time: | 5-8 work days |
Packaging Details: | wooden packaging |
Usage: | Digital Cable Tester |
Cable Type: | Shielded |
Power: | Electricity |
Customized: | Yes |
I. System purpose : The portable cable fault location system Suitable for system testing of medium and low voltage fault cables below 35kv.1250J compact power can breakdown fault cables in 7seconds.measuring rough distance of underground fault cable , locating precisely fault point, and detecting underground cable path and depth.easing using and operating.
II. System Configuration
Product name | Model No. | Qty.(unit) | Function |
cable fault pre locator | XHGG502A2 | 1 | For underground cable fault rough distance measurement |
cable fault pinpointer | XHDD503C | 1 | By Acoustic-magnetic synchronization method to accurately locate the fault point of the cable and detect the path , with powerful background noise reduction(BNR) and compass indication functions |
high voltage pulse generator | XHHV535-2L | 1 | surge discharging for underground cable fault locating & DC high voltage withstand voltage test equipment. |
Product Features
High voltage pulse gennerator XHHV535-2L
mainly used for shock discharge during low-voltage cable fault testing. The pulse generator adopts humanized design operation mode, high-precision dedicated high-voltage electronic components and high-frequency high-voltage technology, which is easy to operate, light in weight and easy to carry. It integrates the energy storage capacitor, DC high voltage source, and discharge ball gap. The operation of this equipment is safe and reliable, with automatic protection functions of over-current, overvoltage and overheating, it can truly achieve the effect of not being damaged by impact, and it can also work normally with high voltage to ground. Low voltage pulse generator is equipped with a time relay, and the discharge time interval can be arbitrarily set within 0-100 seconds. When working, the high-voltage pulse output is uniform and controllable, high-voltage side voltage measurement, make the result real-time and accurate. Unique high-voltage measurement design, in the stop state, the voltmeter can indicate the capacitor voltage in real time. The user can observe the residual voltage while discharging, until the voltage value returns to zero, and finally make the discharge more thorough.
cable fault pinpointer XHDD503C
Cable fault location instrument uses the acoustic and magnetic
synchronization method to determine the power cable fault point.
The electronic flashover is generated by the impact discharge
generator, picked up and amplified by the corresponding probe, and
the precise location of the fault point is determined by auditory
and visual judgment.
It is a device that completes the precise positioning of the cable
fault point within the rough measurement range and collects the
acoustic and magnetic time difference. It integrates positioning
technology, path-assisted testing and other technologies, providing
multiple test modes and rich and diverse prompt information to
efficiently and accurately complete cable fault location
1 | Filter parameters | All-pass: 100Hz~1600Hz. Low pass: 100Hz~300Hz. Qualcomm: 160Hz~1600Hz. Bandpass: 200Hz~600Hz. |
2 | Channel gain | 8 levels adjustable. |
3 | Magnetic channel gain | 8 levels adjustable. |
4 | Output gain | 16 levels (0~112db) |
5 | Output impedance | 350Ω |
6 | Acoustomagnetic positioning accuracy | less than 0.2m. |
7 | Path identification accuracy | less than 0.5m. |
8 | Power supply | 4*18650 standard lithium batteries. |
9 | Standby time | more than 8 hours. |
10 | Volume | 428L×350W×230H |
11 | Weight | 6.5kg. |
12 | Ambient temperature | -25~65ºC; Relative humidity: ≤90%. |
Cable fault prelocator XHGG502A2
★ Display: 10.1-inch touch screen,Windows system;
★ Function: Test cable wave speed, cable length and fault distance;
Automatic testing range setting, automatic waveform analysis to
display testing distance; Powerful data processing and massive test
waveform storage.
★Testing methods: Low voltage pulse method, high voltage flashover
method
★ Power supply: Charging AC110V~240V, 50Hz/60Hz;Built-in 5200mAH
lithium battery;
★Sampling frequency: 80MHz;
★ Low voltage pulse amplitude: 100V±15%;
★ Distance measurement range: ≥65km;
★ Test range: 300m/1km/5km/25km/65km;
★ Pulse width: 0.1uS/0.50uS/2.50uS/7.25uS/10.0uS;
★Test frequency: 80MHz/40MHz/10MHz/2MHz/1MHz
★ Minimum resolution: 0.10m;
★ Test blind area: ≤20m;
uses an industrial-grade 10.1-inch touch screen and a simple
Windows operating system. It adopts industrial-grade integrated
circuits and devices and has a built-in large-capacity lithium-ion
battery. It is a special instrument for measuring and analyzing the
status and fault distance of power cables. It is stable, reliable
and easy to use.
It uses a combination of modern electronic technology and computer
technology to implement signal filtering, acquisition, data
processing, graphic display, and graphic analysis to complete cable
speed measurement, cable length testing, and cable fault distance
testing.
It is suitable for low-resistance, short-circuit, open-circuit and
disconnection faults of power cables, high-frequency coaxial
cables, street light cables, and buried wires made of various
materials with different cross-sections and media, as well as
high-resistance leakage and high-resistance flashover. Network fault.
![]() |