Categories | Transformer Tester |
---|---|
Certification: | CE, ISO |
Brand Name: | XZH TEST |
Model Number: | XHYY102S |
Place of Origin: | Xi'an, Shaanxi, China |
MOQ: | 1 unit |
Payment Terms: | T/T |
Supply Ability: | 1000pieces/Year |
Delivery Time: | 5-8 days |
Packaging Details: | wooden case |
Model NO.: | XHYY102S |
Appliance: | Oil Analysis |
Output Voltage: | 0~100kv |
Power: | 200W |
Booster Capacity: | 1.5kVA |
Measuring Range: | 0~ 80kv (Customized 100kv) |
Boost Speed: | 2.0-3.5 Kv/S (Adjustable) |
Resting Time: | 15 Min(Adjustable) |
Boost Interval: | 5 Min(Adjustable) |
Transport Package: | Wooden Box with Foam Inside |
Specification: | 465mm*385*mm*425mm |
HS Code: | 9031809090 |
Customization: | Available |
After-sales Service: | Technical Support |
Warranty: | 1 Year |
Transformer Bdv Insulation Oil Tester Three Cup Oil Breakdown Tester for Customization
The insulating oil dielectric strength tester is a scientific
research and technical personnel of our company. According to the
relevant provisions of the national standard GB507-86 and the
industry standard DL-474·4-92DL/T596-1996, it has given full play
to its own advantages. After many field tests and long-term
unremitting Efforts to carefully research and develop
high-accuracy, all-digital industrial instruments. The machine is
easy to operate and beautiful in shape. Due to the use of fully
automatic digital microcomputer control, the measurement accuracy
is high, the anti-interference ability is strong, and it is safe
and reliable.
1. The instrument is controlled by a large-capacity single-chip
microcomputer, and the work is stable and reliable;
2. A wide-range watchdog circuit is installed in the instrument to
prevent crashes;
3. A variety of operation options, the instrument program has two
national standard methods of GB1986 and GB2002 and self-defined
operations, which can adapt to various choices of different users;
4. The oil cup of the instrument is molded by one-time casting of
special glass, which prevents the occurrence of interference
phenomena such as oil leakage;
5. The unique high-voltage terminal sampling design of the
instrument allows the test value to directly enter the A/D
converter, avoiding the error caused in the analog circuit and
making the measurement result more accurate;
6. The instrument has over-current, over-voltage, short-circuit and
other protection functions inside, and has strong anti-interference
ability and good electromagnetic compatibility;
7. Portable structure, easy to move, convenient for indoor and
outdoor use.
Output voltage | 0~80KV/0~100kV (optional) |
Voltage distortion rate | <3% |
Voltage raising speed | 2.0 kV/s, 2.5 kV/s, 3.0 kV/s, 3.5 kV/s four optional |
Standing time | 15min (adjustable) |
Boosting interval | 5 min (adjustable) |
Boosting frequency | 1~9 time(s) (optional) |
Booster capacity | 1.5KVA |
Measuring accuracy | ±3% |
Supply voltage | AC220V±10% 50Hz±1 Hz |
Power | 200W |
Applicable temperature | 0ºC~45ºC |
Applicable humidity | Ethernet: IEEE802.3 |
Instrument volume | <75%RH |
Weight | ~62kg |
Overall dimension | 465×385×425mm Weight:25 kg |
![]() |